Table 2a
Gallons Per Minute Flow Rate Through Pipe
Pipe Size |
Liquid Flow Rate For A 600 Feet Per Minute Velocity - (GPM) |
|||
Schedule 40 |
Schedule 80 |
Schedule 160 |
Dbl. Extra Hvy. |
|
1/8 |
1.77 |
1.12 |
¾ |
¾ |
1/4 |
3.24 |
2.24 |
¾ |
¾ |
3/8 |
5.95 |
4.38 |
¾ |
¾ |
1/2 |
9.47 |
7.29 |
5.31 |
1.56 |
3/4 |
16.6 |
13.5 |
9.22 |
4.61 |
1 |
26.9 |
22.4 |
16.3 |
8.79 |
1 1/4 |
46.6 |
40.0 |
32.9 |
19.6 |
1 1/2 |
63.4 |
55.0 |
43.8 |
29.6 |
2 |
104.5 |
92.0 |
69.8 |
55.3 |
2 1/2 |
149.2 |
132.0 |
110.5 |
76.7 |
3 |
230.3 |
205.8 |
168.5 |
129.4 |
3 1/2 |
308.0 |
276.9 |
¾ |
182.1 |
4 |
396.6 |
358.2 |
289.2 |
243.1 |
5 |
623.2 |
566.8 |
455.1 |
403.9 |
6 |
900.0 |
812.1 |
658.9 |
586.7 |
8 |
1558.5 |
1422.5 |
1135.8 |
1156.4 |
10 |
2456.5 |
2238.0 |
1767.8 |
¾ |
12 |
3486.9 |
3166.4 |
2508.7 |
¾ |